Figure 2-25
Diagram for cabinet deployment
≥1000mm
800mm
00m
m
m
≥1000mm
≥800mm
600mm
600mm
600mm
m
Device Clearance Requirements
The USG9560 chassis is 14 U high and requires front and back maintenance mode. The
device must meet the following clearance requirements:
l
Airflow
–
A minimum of 750 mm between the device and the equipment room wall and
between two neighboring devices
–
A minimum of 2 U between devices installed in the same cabinet, between the top-
most device and the cabinet top, and between the bottom-most device and the
cabinet bottom
l
Maintenance
A minimum of 700 mm between devices and between devices and walls
NOTE
The length of three holes on the mounting rails is 1 U, which is equivalent to 44.45 mm.
2.3.2 Installing the Chassis into the Cabinet