Procedure
Step 1 Choose Maintenance > Device Mgmt. > Data Re-Collection.
Step 2 Select the type of the data to be collected and set the collection period.
Step 3 Select the name of the device whose data is to be collected and click Collect
Data.
Step 4 Wait until all data is gathered. On the Monitoring page, query the collection
result.
----End
7.4.10 Adjusting the Total Energy Yield
This section applies to V300R001C00.
Procedure
Step 1 Choose Maintenance > Device Mgmt. > Adjust total energy yield.
Step 2 Set Adjust total energy yield(kWh), select the name of the device whose total
energy yield needs to be adjusted, and click Submit.
----End
7.4.11 Force Start
This section does not apply to V300R001C00.
Procedure
Step 1 Choose Maintenance > Device Mgmt. > Force Start and click Starting up. This
operation will interrupt ongoing services in the array. Exercise caution when
performing this operation.
NO TE
● The array-level force start operation lasts 180 minutes. The SmartLogger needs to
maintain the array-level force start state. The default status is Idle. After a force start
task is started, the SmartLogger periodically collects the SOC value of each battery rack.
If the SOC value is lower than 50%, the SmartLogger remains in the Force starting...
state. If the SOC value of each battery rack exceeds 50% or the maximum protection
duration for force start is exceeded, the SmartLogger restores the force start state to
Idle.
● After a force start task is started, you can stop the task. In this scenario, devices in the
array stop force start and return to their original status.
● After an array-level force start task is started, if new devices are connected and cannot
be automatically started or some devices restart, the SmartLogger delivers a force start
command at an interval of 5 minutes to ensure that the devices can identify the force
start state.
----End
7.5 Device Disposal
SmartLogger3000
User Manual
7 Device Maintenance
Issue 10 (2022-08-20)
Copyright © Huawei Technologies Co., Ltd.
252