Parameter
Description
Remarks
cosφ-P/Pn exit
voltage
Specifies the voltage threshold for
exiting reactive power compensation
based on the cosφ-P curve.
-
Reactive power
adjustment time
Specifies the adjustment time for the
reactive power to reach the target
value during reactive power
adjustment.
-
Reference Power Parameters
Parameter
Setting Description
Apparent power
baseline
Set the apparent power baseline for power scheduling. The value
cannot be greater than the maximum apparent power.
Active power baseline
Set the active power baseline for power scheduling. The value cannot
be greater than the maximum active power.
Calibrating the Energy Yield
Parameter
Setting Description
Total energy yield
adjustment
A calibrating coefficient for the total energy yield to ensure that the
reported energy yield is consistent with the actual energy yield at the
grid-connection point
Adjustment of total
power supply from grid
A calibrating coefficient for the total power supply from the grid to
ensure that the reported energy yield is consistent with the actual
power supply from grid
6.3.9.2 Characteristic Curve
Step 1 Choose Monitoring > PCS > Characteristic Curve, set characteristic curve
parameters, and click Submit.
Characteristic Curve
Name
Setting Description
LVRT characteristic curve
Configure this characteristic curve based on the
power grid standard.
NOTE
The SmartLogger supports only the curve configuration
for LVRT that lasts no more than 60s. If a power grid
standard requires that LVRT be longer than 60s, LVRT
characteristic curve is not displayed for the grid code.
SmartLogger3000
User Manual
6 WebUI Operations
Issue 10 (2022-08-20)
Copyright © Huawei Technologies Co., Ltd.
160