Configuration File Import/Export
●
This parameter is displayed when Connection is set to Enable.
●
You can contact the vendor to obtain the CID files of the SmartLogger and
the peer controller. Compress the CID files of the SmartLogger and the peer
controller into a .zip configuration package, and click Import Config. Import
the configuration package. After the configuration is parsed successfully, the
Device name, Controller type, Controller name, Configuration status, and
Last import time are displayed. For details about GOOSE interconnection and
interfaces, see the SmartLogger IEC61850 GOOSE Protocol Interface
Description.
If the configuration file is imported and parsed successfully, the configuration
status is Configured. If the configuration file import fails, contact the vendor
of the peer controller to obtain the correct CID file.
Message
Indicating
Failed
Configuration
Message Indicating Failed
Configuration
Suggestion
Import failed.
The
configuration
file is
incomplete.
The CID file of the local or
peer device is missing.
Contact the vendor of the
peer controller to obtain
the correct CID file.
Import failed.
The
configuration
file is not for
this device.
The file does not match the
vendor or the device type.
Import failed.
Unable to parse
the
configuration
file.
The CID file format is
incorrect. Parsing failed or
no matching signal is
found.
●
Click Export Config. to obtain the ICD file of the current SmartLogger version.
The CID file is exported at the same time if it has been imported successfully.
6.3.7 Setting MBUS Parameters
Procedure
Step 1 Set access parameters.
●
Set parameters for the built-in MBUS and click Submit.
SmartLogger3000
User Manual
6 WebUI Operations
Issue 10 (2022-08-20)
Copyright © Huawei Technologies Co., Ltd.
114