7.3 Alarm List
Alarm
ID
Alarm Name Alarm
Severity
Alarm
Sub-ID
Cause
Suggestions
1100
Active Power
Scheduling
Instruction
Exception
Major
4
In DI active
scheduling
mode of the
active power,
the four DI
ports read
command
combinations
that are not
configured.
1. Check that cables are
connected correctly to the DI
ports.
2. Enter the configuration page
of the DI active scheduling
mode for active power
control, and view the current
DI signal configuration
mapping table. Contact the
power grid company and
verify that the combination
configurations in the table are
complete and meet the
requirements of the company.
Major
5
In the remote
active power
scheduling
mode, the
SmartLogger
cannot
receive the
active power
scheduling
command, or
the received
active power
scheduling
command is
abnormal.
1. Check whether the
communication network
between the SmartLogger
and the plant scheduling
control system is normal.
2. Check whether the active
power scheduling commands
received by the SmartLogger
from the plant scheduling
control system are correct,
such as the command format
and protocol type.
1101
Reactive
Power
Scheduling
Instruction
Exception
Major
4
In DI reactive
scheduling
mode of the
reactive
power, the
four DI ports
read
command
combinations
that are not
configured.
1. Check that cables are
connected correctly to the DI
ports.
2. Enter the configuration page
of the DI reactive scheduling
mode for reactive power
control, and view the current
DI signal configuration
mapping table. Contact the
power grid company and
verify that the combination
configurations in the table are
complete and meet the
requirements of the company.