Parameter
Description
Q/S during power
limiting of solar
inverter in case of
reactive power
scheduling timeout (%)
The default value is 0.000. After Limit solar inverter
power upon reactive power scheduling timeout is
enabled, if the communication between the
SmartLogger and the scheduling backend is
interrupted for a period longer than the set value of
Reactive power scheduling timeout threshold for
triggering solar inverter power limiting, the
SmartLogger limits the reactive power of the inverter
based on the set value of this parameter.
Q/S during power
limiting of ESS in case
of reactive power
scheduling timeout (%)
The default value is 0.000. After Limit solar inverter
power upon reactive power scheduling timeout is
enabled, if the communication between the
SmartLogger and the scheduling backend is
interrupted for a period longer than the set value of
Reactive power scheduling timeout threshold for
triggering solar inverter power limiting, the
SmartLogger limits the reactive power of the PCS
based on the set value of this parameter.
Power Factor Closed-Loop Control (Old Policy)
NO TICE
Before setting this parameter, ensure that the power meter is correctly connected
to the SmartLogger.
Parameter
Description
Reactive power control
mode
Set this parameter to Power factor closed-loop
control (old policy).
Target power factor
Specifies the target value for the adjustment power
factor of the power meter.
Adjustment period
Specifies the interval for sending adjustment
commands by the SmartLogger.
Adjustment deadband
Specifies the adjustment power factor precision.
NOTICE
This parameter is valid only when the power factor of the
power meter is greater than 0.9.