Parameter
Setting Description
Exhaust fan control
After started, the exhaust fan will automatically stop in 1 hour. If a
combustible gas alarm is generated, the exhaust fan cannot be
stopped. The exhaust fan cannot be manually started after the fire
response is triggered until the fire alarm is cleared or 24 hours
later.
Fire Suppression
NO TE
Only the LUNA2000-2.0MWH Series Smart String ESS supports DC output power
distribution.
Parameter
Setting Description
DC output distribution
● Starting up: Enable the DC output power distribution to supply
48 V DC power to the battery pack fan, BMU, and ESC
monitoring system.
● Stop: Disable the DC output power distribution to stop
supplying 48 V DC power to the battery pack fan, BMU, and ESC
monitoring system.
NO TE
Only the LUNA2000-200KWH Series Smart String ESS supports the temperature alarm
threshold settings.
Parameter
Setting Description
Temperature alarm
threshold
Specifies the temperature threshold for triggering a fire alarm and
processing fire response logic.
6.3.11 Setting ESU Parameters
This section does not apply to V300R001C00.
Procedure
Choose Monitoring > ESS > ESU > Running Param., set running parameters and
click Submit.