Parameter
Description
Remarks
VSG excitation
damping
coefficient
The default value is 0. Specifies the power factor
that prevents the voltage change of the virtual
synchronous generator.
Wired carrier
synchronization
Enables or disables wired carrier synchronization.
The default value is Disable.
-
Delay
compensation
for wired carrier
synchronization
The default value is 0. Specifies the value of delay
compensation for wired carrier synchronization.
This parameter is
displayed when Wired
carrier synchronization
is set to Enable.
Wired power
frequency
synchronization
Enables or disables wired power frequency
synchronization. The default value is Disable.
-
Delay
compensation
for wired power
frequency
synchronization
The default value is 0. Specifies the value of delay
compensation for wired power frequency
synchronization.
This parameter is
displayed when Wired
power frequency
synchronization is set to
Enable.
Voltage
adjustment
value for VSG
synchronous
control (%)
The default value is 0. Specifies the adjustment
value of the PCS control output voltage in VSG
mode.
● Value range: [–10.0,
10.0]
● The value is adjusted
based on the offset
per unit value. For
example, if the rated
output voltage is 800
V and the output
voltage needs to be
adjusted to 805 V, the
adjustment value is
5/800 x 100%.
Frequency
adjustment
value for VSG
synchronous
control (%)
The default value is 0. Specifies the adjustment
value of the PCS output frequency in VSG mode.
● Value range: [–10.0,
10.0]
● The value is adjusted
based on the offset
per unit value. For
example, if the rated
output frequency is
50 Hz and the output
frequency needs to be
adjusted to 50.5 Hz,
the adjustment value
is 0.5/50 x 100%.
SmartLogger3000
User Manual
6 WebUI Operations
Issue 10 (2022-08-20)
Copyright © Huawei Technologies Co., Ltd.
157