Alarm
ID
Alarm Name Alarm
Severity
Alarm
Sub-ID
Cause
Suggestions
1129
SmartLogger
Certificate
Invalid
Warning 1
The
SmartLogger
digital
signature
certificate is
invalid.
Check the time or change the
digital signature certificate.
1130
SmartLogger
Certificate
About to
Expire
Warning 1
The
SmartLogger
digital
signature
certificate is
about to
expire.
Change the digital signature
certificate in time.
1131
SmartLogger
Certificate
Expired
Major
1
The
SmartLogger
digital
signature
certificate has
expired.
Change the digital signature
certificate immediately.
1132
Storage not
Match Alarm
Major
1
There exists a
Smart Battery
ESC that is
not
completely
connected to
the DC bus.
1. Referring to the cable
connection check topology
view, locate the Smart Battery
ESC that has the cabling
problem.
2. Turn off the battery input
switch, the DC and AC
switches in the LV panel. Wait
for 5 minutes. Verify that no
electricity is present using a
multimeter before checking
the DC bus cable connection
of the battery.
1134
PCS not
Match Alarm
Major
1
There exists a
Smart Battery
PCS that is
not
completely
connected to
the DC bus.
1. Referring to the cable
connection check topology
view, locate the Smart Battery
PCS that has the cabling
problem.
2. Turn off the battery input
switch, the DC and AC
switches in the LV panel. Wait
for 5 minutes. Verify that no
electricity is present using a
multimeter before checking
the DC bus cable connection
of the battery.
SmartLogger3000
User Manual
7 Device Maintenance
Issue 10 (2022-08-20)
Copyright © Huawei Technologies Co., Ltd.
239