NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
86
Alarm
ID
Alarm
Name
Alarm
Severity
Impact
Possible Causes
Solution
capacity of the
NetCol5000-A020 is
insufficient or the heat
load is high.
4.
The ambient temperature
is higher than the upper
alarm threshold.
temperature.
a052
Supply-air 1
temp invalid
Supply-air 2
temp invalid
Major
The alarm
is
generated.
1.
The supply air
temperature sensor is
faulty.
2.
Cables to the supply air
temperature sensor are
loose or damaged.
1.
Maintain or replace
the supply air
temperature sensor.
2.
Check cables to the
supply air temperature
sensor.
a076
Humidifier
alarm
Major
The alarm
is
generated,
and the
humidifier
shuts down.
1.
The humidifier is faulty.
2.
Cables to the humidifier
are loose or damaged.
1.
Maintain or replace
the humidifier. Clear
the accumulated
runtime.
2.
Check cables to the
humidifier.
NOTE
After the alarm is cleared,
click
Manual clear
on the
alarm page.
a077
Indoor fan
1/2/3/4/5/6/7/
8 fault
Major
The alarm
is
generated.
1.
Cables to indoor fan are
loose or damaged.
2.
The indoor fan fuse is
faulty.
3.
Indoor fan is faulty.
1.
Check cables to the
indoor fan.
2.
Change the fuse.
3.
Maintain or replace
the indoor fan.
a078
Full water
Critical
The alarm
is
generated,
and the
system
shuts down.
1.
The float is faulty or
stuck.
2.
Cables to the float are
loose or damaged.
3.
The condensate pump is
faulty, or the drainage
capacity of the
condensate pump
decreases. (If no
condensate pump is
configured, ignore this
check item.)
4.
The drainpipes to the
condensate pump do not
work properly. (If no
condensate pump is
configured, the
drainpipes may be
blocked or frozen.)
1.
Maintain or replace
the float or clear the
obstacles.
2.
Check cables to the
float.
3.
Maintain or replace
the condensate pump.
(If no condensate
pump is configured,
ignore this operation.)
4.
Clean the drainpipes
(by removing
obstacles around or in
the drainpipes).
a079
Drain
Major
The alarm
is
1.
The float is faulty or
stuck.
1.
Maintain or replace
the float or clear the