5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
96
−
If no, go to
Step 2
.
If there are no alarms, go to
Step 2
.
Step 2
Check for any startup requirement for humidifier on the LCD.
Tap
Running
>
Status
to check whether the humidifier is started.
If no, tap
Settings
>
System Settings
>
T/H Sensor
, set the humidify to environmental
hu 5%, then the humidifier can run normally, troubleshooting is complete. If
does not run, go to
Step 3
.
If yes, go to
Step 3
.
Step 3
Check whether the humidification function is enabled.
If no, tap
Settings
>
System Settings
>
System Control
to enable the humidification
function and check whether the fault is rectified.
−
If yes, troubleshooting is complete.
−
If no, go to
Step 4
.
If yes, go to
Step 4
.
Step 4
Check whether the circuit breakers are switched on.
If no, switch on the circuit breakers and check whether the fault is rectified.
−
If yes, troubleshooting is complete.
−
If no, go to
Step 5
.
If yes, go to
Step 5
.
Step 5
Check whether the humidifier cylinder is damaged.
If yes, replace the humidifier cylinder by referring to
5.6.4 Replacing the Humidifier
Cylinder
and then check whether the fault is rectified.
−
If yes, troubleshooting is complete.
−
If no, go to
Step 6
.
If no, go to
Step 6
.
Step 6
Contact Huawei technical support.
----End
5.5.6 The Heating Function Is Unavailable
Possible Causes
The electric heater alarm exists.
An electric heater does not need to start.
Electric heater function is not enabled.
The electric heater temperature switch is being protected.
The circuit breaker of electric heater is not switched on.
An electric heater is burnt out.