NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
3 Installation Guide
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
56
Figure 3-35
Cables routed outside the cabinet
(1) Cold aisle side
(2) Hot aisle side
The T/H sensor should be placed at a place 1.5 m to the ground, and fixed securely using cable ties.
A maximum of three T/H sensors can be connected in hot and cold aisle respectively.
Step 2
Set DIP switches of the T/H sensor,
Table 3-12
lists how to set.
Table 3-12
DIP switches of the T/H sensor
Positi
on
Name
Addr
ess
DIP Switch Sequence
1
2
3
4
5
6
Return
air
Return air T/H 1
1
ON
OFF
OFF
OFF
OFF
OFF
Cold
aisle
Cold aisle T/H 1
11
ON
ON
OFF
ON
OFF
OFF
Cold aisle T/H 2
12
OFF
OFF
ON
ON
OFF
OFF
Cold aisle T/H 3
13
ON
OFF
ON
ON
OFF
OFF
Hot
Hot aisle T/H 1
21
ON
OFF
ON
OFF
ON
OFF