NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
85
Alarm
ID
Alarm
Name
Alarm
Severity
Impact
Possible Causes
Solution
load is high.
5.
The ambient temperature
is higher than the upper
alarm threshold.
a049
Supply-air LT Warning
The alarm
is
generated.
1.
The supply air low
temperature alarm
threshold is
inappropriate for the
working conditions.
2.
The temperature
displayed on the LCD is
different from the actual
temperature.
3.
The supply air
temperature sensor is
faulty.
4.
The air filters are
blocked.
5.
The ambient temperature
is below the alarm
threshold for low
ambient temperatures.
1.
Adjust the supply air
low temperature alarm
threshold.
2.
Calibrate or replace
the supply air
temperature sensor.
3.
Check cables to the
supply air temperature
sensor.
4.
Calibrate or replace
the air filters.
5.
Check the ambient
temperature.
a050
Cold aisle HT
Critical
The alarm
is
generated.
1.
The high temperature
alarm threshold for the
cold aisle is
inappropriate for the
working conditions.
2.
The temperature
displayed on the LCD is
different from the actual
temperature.
3.
The refrigeration
capacity of the
NetCol5000-A020 is
insufficient or the heat
load is high.
4.
The ambient temperature
is higher than the upper
alarm threshold.
1.
Adjust the high
temperature alarm
threshold for the cold
aisle.
2.
Maintain or replace
the T/H sensor.
3.
Add more
NetCol5000-A020
units.
4.
Check the ambient
temperature.
a051
Hot aisle HT
Critical
The alarm
is
generated.
1.
The high temperature
alarm threshold for the
hot aisle is inappropriate
for the working
conditions.
2.
The temperature
displayed on the LCD is
different from the actual
temperature.
3.
The refrigeration
1.
Adjust the high
temperature alarm
threshold for the hot
aisle.
2.
Calibrate or replace
the T/H sensor.
3.
Add more
NetCol5000-A020
units.
4.
Check the ambient