5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
80
Alarm
ID
Alarm
Name
Alarm
Severity
Impact
Possible Causes
Solution
compressor
shuts down
forcibly.
is faulty.
3.
The solenoid valve is
faulty.
4.
The filter dryer is
blocked.
5.
The expansion valve is
blocked.
6.
The refrigerant leaks.
switch.
3.
Maintain or replace
the solenoid coil or
solenoid valve.
4.
Maintain or replace
the filter dryer.
5.
Maintain or replace
the expansion valve.
6.
Check and rectify any
leakages. Charge
refrigerant after
maintenance or
replacement.
a011
Comp suction
LP lock
Critical
The alarm
is
generated,
and the
compressor
is locked
and not
allowed to
be started.
The Comp suction LP alarm
is triggered for the
compressor multiple times
within a period.
Clear this alarm using the
solutions for alarm a010.
NOTE
After the alarm is cleared,
click
Manual clear
on the
alarm page.
a012
Comp dis HT
Major
The alarm
is
generated,
and the
compressor
shuts down
forcibly.
1.
Cables to the high
temperature switch are
loose or damaged.
2.
The high temperature
switch is faulty.
3.
Outdoor fans are faulty.
4.
The condenser is
blocked.
5.
The refrigerant leaks.
6.
The refrigeration
capacity of the
NetCol5000-A020 is
insufficient or the heat
load is high.
1.
Check cables to the
high temperature
switch.
2.
Maintain or replace
the temperature
switch.
3.
Maintain or replace
the outdoor fans.
4.
Clean the condenser.
5.
Check and rectify any
leakages. Charge
refrigerant after
maintenance or
replacement.
6.
Add more
NetCol5000-A020
units.
a013
Comp dis HT
lock
Critical
The alarm
is
generated,
and the
compressor
shuts down
forcibly.
The Comp dig HT alarm is
triggered for the compressor
multiple times within a
period.
Clear this alarm using the
solutions for alarm a012.
NOTE
After the alarm is cleared,
click
Manual clear
on the
alarm page.
a014
Comp short
period
Warning
The alarm
is
1.
The shortest running
period and shortest
1.
Adjust the shortest
running period and