NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
95
Figure 5-2
Fan fuse position
(1) Fan
fuse
The fuses from top to bottom are FU9 to FU16, corresponding to fan 1 to fan 8
After treatment, check whether the fault is rectified. If yes, troubleshooting is complete.
If no, go to
Step 5
.
Step 5
Contact Huawei technical support.
----End
5.5.5 Humidification Fails
Possible Causes
Humidifier alarm exists.
A humidifier does not need to start.
Humidification function is not enabled.
The humidifier circuit breaker is disconnected.
The humidifier cylinder is damaged.
Procedure
Step 1
Check whether there are humidifier alarms.
If yes, deal with it by referring to
5.4 Alarm Reference
and then check whether the fault
is rectified.
−
If yes, troubleshooting is complete.