5.6.4 Replacing the Humidifier Cylinder
Prerequisites
Recommended tools: a Phillips screwdriver, an inner hexagon wretch.
The humidifier cylinder needs to be replaced.
A spare and functional humidifier cylinder is available.
Context
The rear door is opened for rear-access maintenance.
After the equipment is powered off, wait for a period and replace the humidifier tank until the
pipeline temperature is approximate to the room temperature to avoid scald.
Procedure
Step 1
Press down the drainage button to "I" on one side of the electrical control box to drain the
water out of the humidifier cylinder.
Step 2
Tap
Shutdown
on the main menu, switch off the main circuit breaker QF1 and the front end
circuit breaker.
Exercise cautions when performing operations on the equipment because the equipment is
under power.
Remove the rear door and the air filters when switch off the main circuit breaker QF1.
Step 3
Remove the hose clamp fixing hoses and steam hose above the humidifier cylinder in
sequence as shown in 1 of
Figure 5-7
.