NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
3 Installation Guide
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
26
Table 3-9
Recommended pipe specifications
Pipe Length (m)
Recommended Diameter
for Gas Pipes (inch)
Recommended Diameter
for Liquid Pipes (inch)
L ≤ 25
5/8
1/2
If L is longer than 25 m, contact Huawei technical support.
Electric Connection Precautions
Ensure that connections of all power cables, control cables, and ground cables comply
with the local electrical code and that the cable specifications comply with the local
cable layout rules.
For details about the currents in full load, see the NetCol5000-A020 nameplate.
Only trained and qualified personnel are allowed to connect cables. Installation
personnel must take protective measures, for example, wearing protective gloves.
All precision air conditioners must be reliably grounded.
3.1.4 Installation Layout
Layout principles for installing the NetCol5000-A020 are as follows:
If the outdoor unit is placed higher than the indoor unit, the maximum vertical distance
between them is 10 m. To ensure system reliability, make an oil trap every 5 m to 6 m
along pipes in the vertical direction.
Figure 3-1
shows positions of oil traps and inverted
traps. For more specifications, see
Table 3-6
.
If the indoor unit is placed higher than the outdoor unit, the maximum vertical distance
between them is 5 m.
The inverted trap should be higher than the top copper pipe of the condenser in the outdoor
unit.