NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
121
5.6.11 Replacing the Float
Prerequisites
The float needs to be replaced.
A spare and functional float is available.
Context
The front door is opened for front-access maintenance.
Procedure
Step 1
Tap
Shutdown
on the main menu, switch off the main circuit breaker QF1 and the front end
circuit breaker.
Exercise cautions when performing operations on the equipment because the equipment is
under power.
Remove the rear door and the air filters when switch off the main circuit breaker QF1.
Step 2
Remove the front door, cables to the controller, and ground cables.
Step 3
Remove the fan at the most bottom of the cabinet by referring to
5.6.2 Replacing an Indoor
Fan
.
Step 4
Remove the screw fixing the float, take out the float, and disconnect float cables from the
connectors, as shown in 1 and 2 of
Figure 5-17
.