NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
101
Procedure
Step 1
Tap
Shutdown
on the main menu, switch off the front end circuit breaker.
Exercise cautions when performing operations on the equipment because the equipment is
under power.
Step 2
Remove the rear door.
Step 3
Turn the plates on both sides for fixing the upper air filter, as shown in step 1 of
Figure 5-3
.
Step 4
Draw out the air filter, as shown in step 2 of
Figure 5-3
.
Figure 5-3
Removing the air filter
Step 5
Draw out the lower air filter using the same way.
Step 6
Install new air filters following the air flow direction instruction on the air filter frame.
Step 7
Install the rear door.
----End
Follow-up Procedure
After powering on, choose
Maint
>
Performance Maint
on the main menu to clear the
accumulated running time of the air filters.