NetCol5000-A020 Air Cooled In-row Precision Air
Conditioner
User Manual
5 System Operation and Maintenance
Issue 01 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
87
Alarm
ID
Alarm
Name
Alarm
Severity
Impact
Possible Causes
Solution
abnormal
generated,
and the
system
shuts down.
2.
Cables to the float are
loose or damaged.
3.
The condensate pump is
faulty, or the drainage
capacity of the
condensate pump
decreases. (If no
condensate pump is
configured, ignore this
check item.)
4.
The drainpipes to the
condensate pump do not
work properly. (If no
condensate pump is
configured, the
drainpipes may be
blocked or frozen.)
5.
Air penetrates the water
pump pipe.
obstacles.
2.
Check cables to the
float.
3.
Maintain or replace
the condensate pump.
(If no condensate
pump is configured,
ignore this operation.)
4.
Clean the drainpipes
(by removing
obstacles around or in
the drainpipes).
5.
Exhaust air in the
water pump pipe.
NOTE
After the alarm is cleared,
click
Manual clear
on the
alarm page.
a083
Surge
protection
board fault
Critical
The alarm
is
generated,
and the
system
shuts down.
1.
The surge protection and
voltage test board is
faulty.
2.
Cables to the surge
protection and voltage
test board are loose or
damaged.
1.
Maintain or replace
the surge protection
and voltage test board.
2.
Check cables to the
surge protection and
voltage test board.
a084
Power fault
Critical
The alarm
is
generated,
and the
system
shuts down.
The NetCol5000-A020
connects to the incorrect
voltage jumper.
Maintain or replace the
voltage jumper.
a085
Route A fuse
disconnect
Critical
The alarm
is
generated,
and the
system
shuts down.
1.
A device on circuit A is
faulty.
2.
The fuse on circuit A is
loose, aged, or
disconnected.
1.
Maintain or replace
the faulty device on
circuit A.
2.
Replace the fuse on
circuit A.
a086
Route B fuse
disconnect
Major
The alarm
is
generated,
and the
system
shuts down.
1.
A device on circuit B is
faulty.
2.
The fuse on circuit B is
loose, aged, or
disconnected.
1.
Maintain or replace
the faulty device on
circuit B.
2.
Replace the fuse on
circuit B.
a087
Route C fuse
disconnect
Critical
The alarm
is
generated,
and the
1.
A device on circuit C is
faulty.
2.
The fuse on circuit C is
loose, aged, or
1.
Maintain or replace
the faulty device on
circuit C.
2.
Replace the fuse on