FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
7 System Commissioning
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
65
Figure 7-29
Loop 2 FAULT RELAY indicator on
3.
Hold the heat detector, and rotate it clockwise to install it to the base.
Step 13
(Optional) Check whether the fire alarm signals are reported to the management system.
Step 14
Flip the
Enable Control
key rightwards, reset the extinguishant control panel by pressing
Reset
on it, and then flip the
Enable Control
key leftwards to reset the key.
----End