FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
7 System Commissioning
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
64
Step 11
Simulate a cable disconnection fault for the smoke detector.
1.
Check whether the extinguishant control panel displays any alarm. If an alarm is
displayed, clear the alarm before performing follow-up operations.
2.
Hold the smoke detector, and rotate it counterclockwise to remove it from the base.
The extinguishant control panel reports a loop 1 FAULT RELAY, and the loop 1 FAULT RELAY
indicator turns on.
Figure 7-28
Loop 1 FAULT RELAY indicator on
3.
Hold the smoke detector, and rotate it clockwise to install it to the base.
Step 12
Simulate a cable disconnection fault for the heat detector.
1.
Flip the
Enable Control
key rightwards, reset the extinguishant control panel by
pressing
Reset
on it, and then flip the
Enable Control
key leftwards to reset the key.
2.
Hold the heat detector, and rotate it counterclockwise to remove it from the base.
The extinguishant control panel reports a loop 2 FAULT RELAY, and the loop 2 FAULT RELAY
indicator turns on.