FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
7 System Commissioning
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
63
Figure 7-26
Manual gas release button
4.
During the countdown, if you press the extinguishant abort button, the countdown stops.
If you rotate the extinguishant abort button clockwise again to reset the button, the
countdown restarts from zero.
Figure 7-27
Extinguishant abort button
5.
After the 30s countdown ends, a driver signal is sent to the electrical actuator.
The electrical actuator ejector pops up to 11-mm long.
Reinstall the yellow protective cover, and reset the extinguishant abort button to the state when it is
not pressed down.
6.
Reset the ejector of the electrical actuator.
7.
Press
Processor Reset
on the extinguishant control panel to reset the panel.
8.
Reinstall the electrical actuator on the container valve.