When powering on and commissioning the 30 kW chilled water precision air conditioner,
you are not allowed to modify the initial configurations of the 30 kW chilled water
precision air conditioner unless you are authorized by onsite Huawei engineers.
For the initial DIP switch configuration for the remote temperature sensor, see
Initial DIP Switch Configuration for T/H Sensors
For the initial DIP switch configuration for the main control board, see
Configuration for the Main Control Board
For the initial teamwork configuration, see
9.2.2.3 Teamwork Initial Configuration
For the initial configuration of temperature and humidity, see
9.2.2.3 Teamwork Initial Configuration
9.2.2.4 Initial Configuration of Temperature
must be configured after power-on.
Step 3
Tap
Indicates
on the main screen, and tap
Confirm
on the dialog box that appears. If the start
succeeds, the system prompts that the command is successfully executed.
----End
9.2.2.1 Initial DIP Switch Configuration for T/H Sensors
Prerequisites
You have powered on the 30 kW chilled water precision air conditioners.
Preparations
Tools: none
Document required: initial DIP switch settings table for the remote T/H sensor of the 30 kW
chilled water precision air conditioner
Skill requirement: cooling engineer
For the tables, see the initial configuration parameter manual for the solution in use.
Context
Each 30 kW chilled water precision air conditioner is equipped with three remote T/H sensors
at the air return vent. A maximum of six remote T/H sensors can be configured.
You need to set the DIP switches for the remote T/H sensors before using the sensors.