FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
6 Power-On Commissioning
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
40
System
Check Item Content
Check Standard
UPS
MDU
The screen is free from erratic display or
missing characters.
Settings meet the requirements of the
current scenario.
The mains voltage, power, current, power
factor, electricity energy, and switch status
are properly displayed.
The branch current, electricity energy, and
switch status are properly displayed.
The communication between the MDU
and monitoring board is normal.
There is no active alarm whose severity is
higher than Minor. If there are any alarms,
record the alarms and handle them.
Cooling
system
Chilled
water
precision air
conditioner
Remote
temperatu
re and
humidity
(T/H)
sensor
The indicator is on.
The DIP switch setting is the same as the
initial setting.
Main
control
board
The DIP switch setting is the same as the
initial setting.
Controller
The screen is free from erratic display or
missing characters, and displays no alarm.
The teamwork setting is the same as the
initial setting.
Chiller
Output
function
All output functions are automatic.
Temperat
ure
settings
and
control
precision
The temperature settings and control precision
are appropriate.
Compone
nt layout
All components are installed in the correct
positions.
Settings
of other
functions
Other functions are properly set.