FusionModule1000B Water-Cooled IT Solution
Commissioning Guide
9 Commissioning Core Components
Issue 02 (2017-01-10)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
72
Specifications
Factory
Setting
Remarks
SY16: DO1 output
0
Electricity output from the DO1 port. The value is
an integer ranging from 0 to 8.
0
: no output association
1
: consuming active electricity
2
: releasing active electricity
3
: absorbing reactive electricity
4
: sending out reactive electricity
5
: general active electricity
6
: net value of active electricity
7
: general reactive electricity
8
: net value of reactive electricity
SY23: extremum
interval
10
The interval for extremum statistics is 5-60 min.
SY24: sliding
window time
5
Range: 1-60 min
Step 4
Set multi-rate parameters for the PD510 electricity meter.
Table 9-2
Multi-rate parameter settings for the PD510 electricity meter
Specifications
Factory
Setting
Remarks
E01: multi-rate
enable
Enabled
Enable or disable the multi-rate function.
E02: default setting
enable
Default
The electricity meter has been set before delivery
because the time setting is complicated. You can
customize the settings and restore the default
settings as necessary.
Step 5
Set alarm parameters for the PD510 electricity meter.
Table 9-3
Alarm parameter settings for the PD510 electricity meter
Specifications
Factory
Setting
Remarks
ron: relay n
Set based on the
actual situation.
n = 0-8
Type: alarm mode
Default
Refer to the
DO working type table
provided