7.43 Removing the flexible NIC
Remove the flexible NIC before replacing it with a new one.
Procedure
Step 1
Wear an ESD wrist strap. For details, see
Step 2
Determine the rack number and chassis number of the server to be removed, and label its
panel to prevent misoperations.
Step 3
Power off the 5288 V3. For details, see
.
Step 4
Remove all external cables such as power and network cables.
Step 5
Remove the 5288 V3 and put it on an ESD desktop. For details, see
.
Step 6
Remove the chassis cover. For details, see
7.11 Removing the Chassis Cover
.
Step 7
Remove the I/O module above the flexible NIC. For details, see
Step 8
Remove the cables from the flexible NIC.
Step 9
Loosen the screws on the flexible NIC using a Phillips screwdriver. See step (1) in
.
5288 V3 Server
User Guide
7 Replacing Parts
Issue 26 (2018-11-19)