Upgrading X9700cx I/O module and disk drive firmware
This firmware is only delivered in the mxso-firmware RPM.
IMPORTANT:
The update process requires a capacity block to be power cycled. Since this
involves a power cycle of both X9700c controllers or all X9700cx I/O modules, you cannot access
storage during this time. Therefore, a full system shutdown is required.
IMPORTANT:
Before performing this procedure, ensure that the X9720 Network Storage System
I/O modules are running normally. Use the
exds_stdiag
to verify that the "Path from" from all
running servers is "online" for both X9700c controllers.
To upgrade X9700cx I/O module and disk drive firmware:
1.
Download the RPM.
2.
Install on all servers.
3.
Use the
exds_stdiag
command to verify that all storage units are online. In particular, make
sure both controllers in every X9700c chassis are online. If the path to any controller is "none,"
the controller might not be updated.
4.
Shut down all servers except for the first server. Shut down the first server to single user mode.
5.
Run the update utility (or utilities) located in
/opt/hp/mxso/firmware
. If you are updating
several components, run each update utility one at a time. The update utility depends on the
firmware component being updated as follows:
•
To update the X9700cx I/O module firmware run the following command:
# /opt/hp/mxso/firmware/exds9100cx_scexe -s
•
To update disk driver firmware, run the following command:
# /opt/hp/mxso/firmware/sbdisk_scexe
NOTE:
The
sbdisk_scexe
link is appropriate to firmware supported by the system at first
release. Later models of disk drive might require a different utility.
6.
Press the power buttons to power off the X9700c and X9700cx of all capacity blocks in the
system.
7.
Disconnect all power cables from all X9700cx enclosures until the LEDs on the rear of the units
extinguish. Reconnect the power cables to the enclosures.
8.
Re-apply power to all capacity blocks. Power on the X9700cx first, then the associated X9700c.
The firmware update occurs during reboot so the reboot could take longer than usual (up to
25 minutes). During this time, the seven-segment display will show different codes and the
amber lights of one or both X9700c controllers may come on briefly. This is normal. Wait
until the seven-segment display of all X9700c enclosures goes to the “on” state before
proceeding. If the seven-segment display of an X9700c has not returned to "on" after 25
minutes, power cycle the complete capacity block again.
9.
Reboot the first server.
10.
Run
exds_stdiag
to validate that the firmware is updated. If the firmware is not correct,
exds_stdiag
prints a "*" (asterisk) character at the start of the line in question.
11.
Reboot the other servers.
12.
Run
exds_stdiag
to validate that the system is operating normally.
Upgrading SAS switch module firmware
Complete the following steps:
1.
Logon to the Management Server (172.16.3.1).
92
Upgrading firmware