ALPHABETIC REFERENCE
XI581/2 BUSWIDE OPERATOR INTERFACE
EN2B-0126 (74-3554-8)
94
RESULT: The display window chronologically lists all special days and the
assigned daily programs (if assigned). If a special day does not have
a daily program assignment, that day uses the daily program
specified in the weekly program.
Special Days: Time Program 1
New Year’s Day
Vacation
▲
▲
▲
▲
Epiphany
Workday
■
Shrove Tuesday
1
Ash Wednesday
Workday
■
Good Friday
Halfday
▼
NOTE:
All special days or holidays may not be able to appear in the display
window at the same time. To view special days that do not display,
press the right arrow key to display the next page.
Delete the Special
Day Assignment
5.
Use the arrow keys to move to and highlight the special day or holiday whose
assignment you want to delete. Then press Enter (
↵
) to complete the selection.
RESULT: The controller deletes the special day assignment, and the window
redisplays the special days list.
6.
When you are finished, repeatedly press Cancel (C) to return to the Main Menu.
Change Status (Enable/Disable) Special Days Function
Continued from the special days procedure.
Special Days: Time Program 1
Status
: On
Modify
Delete
Select Status Option
4.
Use the arrow keys to move to and highlight the status value (
On
in this
example) and press Enter (
↵
) to complete the selection.
RESULT: The
Status
field blinks.
5.
Press the plus or minus key to change the entry in the 'Status' field from 'On' to
'Off' or vice versa. Then press Enter (
↵
) to complete the selection.
RESULT: The controller changes the status of the special days feature.
6.
When you are finished, repeatedly press Cancel (C) to return to the Main Menu.
Totalizers
Purpose
To reset the totalizers, display totalizer point value since last reset, and set the
service interval.
Totalizers keep track of when particular points need to be serviced. They count the
number of hours a point has run or the number of energy units it has produced
since it was last serviced. You should reset a data point’s totalizer each time the
data point is serviced to ensure that the totalizer keeps an accurate record.
Access Level
You must have Access Level 3 to perform this task.
Select Totalizers from the
Main Menu
1.
From the Main Menu, use the arrow keys to move to and highlight
Totalizers
.
Press Enter (
↵
) to complete the selection.
RESULT: The display window lists two options for viewing totalizer information.