EVERYDAY OPERATIONS
XI581/2 BUSWIDE OPERATOR INTERFACE
EN2B-0126 (74-3554-8)
28
Totalizers
Service Interval
All Totalizers
Service interval Displays a list of digital points and the number of hours.
All Totalizers
Displays a list of totalizer points and the value of the units
assigned to them.
Select Totalizer Type
2.
Use the arrow keys to move to and highlight the type of totalizer you want to
view. Then press Enter (
↵
) to complete the selection.
RESULT: The display window lists totalizer points.
Service Interval
h
Supply_fan
1267
▲
▲
▲
▲
Exhaust_fan
1257
■
Burner
4761
Htg._zone_pump
736
■
Cafe._hood
123
▼
NOTES:
1.
All totalizer points may not be able to appear in the display window at
the same time.
2.
The appearance of the 'Totalizer' screen differs slightly from that of
the 'Service interval' screen, although they operate the same.
Select a Totalizer Point
3.
Use the arrow keys to move to and highlight the specific totalizer you want to
view. Press Enter (
↵
) to complete the selection.
RESULT: The display window shows detailed information about the selected
totalizer.
Service Interval : 1000 h
Supply fan
: 1267 h
Reset
: Yes/NO
Back
Service interval Number of hours a point can run before the controller
generates a maintenance alarm.
User Address
(Supply fan)
Number of hours the point has run since it was last serviced.
The name of this field reflects the name of the totalizer point
you selected.
Reset
Zero the totalizer point after service.
NOTE:
Additional user-defined text for the point may appear on the second
line.
The "Totalizers" section has more details on totalizer options.
4.
When you are finished, repeatedly press Cancel (C) to return to the Main Menu.