10/01
FSC Safety Manager Installation Guide
55
4.3
Configuration at TPS Universal Station,
Continued
Node-specific
configuration
To configure the node-specific data, return to the NIM Build Type Select
Menu by pressing the [F9 WLK BACK] key (refer back to Figure 4-3).
Select the NODE SPECIFIC CONFIGURATION target. The
Node-Specific Configuration display is shown in Figure 4-5.
Enter and select the desired configuration. Press the [F12 LOAD] key.
ATTENTION
Make sure the network and node numbers entered for this
display match those entered in the UCN Configuration display.
There is no need to configure the redundant FSC-SM device. All
FSC-SM-related information will be automatically transferred to the
"new" primary FSC-SM should there be a failover or switchover to the
backup.
Figure 4-5 – US Node-Specific Configuration display
11 Jun 97 14:05:00 3
PED >>>>>>> POINT:$NM02B13
PAGE 01 OF 03
NODE-SPECIFIC CONFIGURATION
F1=PED
F2=RECALL DISP
F3=
F4=
F5=OVERWRITE
F6=
F7=RECON
F8=PED STATUS
F9 =WLK BACK
F10=WRITE
F11=
F12=LOAD
UNIT:SY
UNENTERED
NETWORK NUMBER
NODE NUMBER
NODE TYPE
(NTWKNUM)
(NODENUM)
(NODETYP)
02
13
PM
APM
HPM
LM
SM
*
*
*
*
*
*
*
*****************************************************************
WARNING: IF THE POINT MIX OR THE SCAN
RATE IS CHANGED, THEN THE NODE'S FULL
DATA BASE WILL BE SET TO ITS DEFAULT.
THE DISPLAY LINES WHICH CAN CAUSE THE
DATA BASE TO BE DEFAULTED ARE STARRED
AND HAVE AN ASTERISK (*) IN COLUMN 80.
*****************************************************************
*
*
*
*
*
*
*
*
SM PLATFORM
(SMPLTFM)
TRICON
FSC
*
Continued on next page
Summary of Contents for FSC-SM
Page 2: ... ...
Page 6: ...iv FSC Safety Manager Installation Guide 10 01 ...
Page 12: ...x FSC Safety Manager Installation Guide 10 01 ...
Page 32: ...20 FSC Safety Manager Installation Guide 10 01 Left blank intentionally ...
Page 54: ...42 FSC Safety Manager Installation Guide 10 01 Left blank intentionally ...
Page 70: ...58 FSC Safety Manager Installation Guide 10 01 Left blank intentionally ...
Page 74: ... ...
Page 75: ... ...