24
FSC Safety Manager Installation Guide
10/01
2.4
Cabling Considerations
Introduction
When installing an FSC Safety Manager System, it is important to
consider:
• conduit and tray shielding and spacing, and
• cable and wire classifications.
Shielding
Conduit or cable trays should be used to route the network trunk line
within the plant for short distances or for several miles. The same conduit
should
not
carry both data and power wiring because of problems created
by electromagnetic interference (EMI). The choice of materials and
configuration for the cable conduit can determine the degree of protection
from this interference.
Table 2-2, showing raceway shielding, is taken from IEEE Standard 518
for the installation of electrical equipment. It compares different types of
conduits and raceways for magnetic field attenuation at 60 Hz and for
electrostatic attenuation at 100 kHz.
Table 2-2 – Raceway shielding
Raceway
Type
Thickness
mm (in.)
60 Hz Magnetic
Field Attenuation
100 kHz Magnetic
Field Attenuation
Ratio
dB
Ratio
dB
Free air
1:1
0
1:1
0
2 inch (5 cm) aluminum conduit
3.91 (0.154)
1.5:1
3.3
2.150:1
66.5
#16 gauge aluminum tray
1.52 (0.060)
1.6:1
4.1
15.500:1
83.9
#16 gauge aluminum tray
1.52 (0.060)
3:1
9.4
20.000:1
86.0
#16 gauge galvan. iron tray
1.52 (0.060)
3.2:1
10.0
22.000:1
86.8
2 inch (5 cm) IPS copper pipe
3.96 (0.156)
3.3:1
10.2
10.750:1
80.6
#16 gauge aluminum tray
1.52 (0.060)
4.2:1
11.5
29.000:1
89.3
#14 gauge aluminum tray
1.90 (0.075)
6:1
15.5
23.750:1
87.5
2 inch (5 cm) metallic tubing
1.65 (0.065)
6.7:1
16.5
3.350:1
70.5
2 inch (5 cm ) rigid galvanized
conduit
3.91 (0.154)
40:1
32.0
8.850:1
78.9
Continued on next page
Summary of Contents for FSC-SM
Page 2: ... ...
Page 6: ...iv FSC Safety Manager Installation Guide 10 01 ...
Page 12: ...x FSC Safety Manager Installation Guide 10 01 ...
Page 32: ...20 FSC Safety Manager Installation Guide 10 01 Left blank intentionally ...
Page 54: ...42 FSC Safety Manager Installation Guide 10 01 Left blank intentionally ...
Page 70: ...58 FSC Safety Manager Installation Guide 10 01 Left blank intentionally ...
Page 74: ... ...
Page 75: ... ...