26
FSC Safety Manager Installation Guide
10/01
2.4
Cabling Considerations,
Continued
Spacing,
continued
Table 2-4 – Tray spacing
Cable
Class
Data 1
mm (in.)
Data 2
mm (in.)
Data 3
mm (in.)
Data 3A
mm (in.)
Data 4
mm (in.)
Data 4A
mm (in.)
Data 1
Note 2
152.4 (6)
152.4 (6)
660.4 (26)
660.4 (26)
Data 2
Note 2
152.4 (6)
152.4 (6)
457.2 (18)
660.4 (26)
Data 3
152.4 (6)
152.4 (6)
0.0 (0)
Note 1
304.8 (12)
Data 3A
152.4 (6)
152.4 (6)
0.0 (0)
203.2 (8)
457.2 (18)
Data 4
660.4 (26)
457.2 (18)
Note 1
203.2 (8)
0.0 (0)
Data 4A
660.4 (26)
660.4 (26)
304.8 (12)
457.2 (18)
0.0 (0)
ATTENTION
Note the following considerations:
• Note 1:
– Data 3 and Data 4 cables may be run in a common tray but should be
separated by a barrier. This barrier does not have to be grounded.
• Note 2:
– Data 1 and Data 2 cables may be in a common tray, provided they are
separated by a grounded steel barrier.
Table 2-5 – Tray/conduit spacing
Cable
Class
Data 1
mm (in.)
Data 2
mm (in.)
Data 3
mm (in.)
Data 3A
mm (in.)
Data 4
mm (in.)
Data 4A
mm (in.)
Data 1
25.4 (1)
101.6 (4)
101.6 (4)
457.2 (18)
457.2 (18)
Data 2
25.4 (1)
101.6 (4)
101.6 (4)
304.8 (12)
457.2 (18)
Data 3
101.6 (4)
101.6 (4)
0.0 (0)
0.0 (0)
203.2 (8)
Data 3A
101.6 (4)
101.6 (4)
0.0 (0)
152.4 (6)
304.8 (12)
Data 4
457.2 (18)
304.8 (12)
0.0 (0)
152.4 (6)
0.0 (0)
Data 4A
457.2 (18)
457.2 (18)
203.2 (8)
304.8 (12)
0.0 (0)
Continued on next page
Summary of Contents for FSC-SM
Page 2: ... ...
Page 6: ...iv FSC Safety Manager Installation Guide 10 01 ...
Page 12: ...x FSC Safety Manager Installation Guide 10 01 ...
Page 32: ...20 FSC Safety Manager Installation Guide 10 01 Left blank intentionally ...
Page 54: ...42 FSC Safety Manager Installation Guide 10 01 Left blank intentionally ...
Page 70: ...58 FSC Safety Manager Installation Guide 10 01 Left blank intentionally ...
Page 74: ... ...
Page 75: ... ...