FSC Safety Manager Installation Guide
10/01
3.2
System Configuration Overview
Introduction
The FSC Safety Manager (FSC-SM) system consists of a redundant Fail
Safe Control (FSC) system fitted with a redundant pair of FSC Safety
Manager Modules (FSC-SMMs).
Each FSC Central Part contains a central processor unit (CPU), a
watchdog (WD) and communication modules (COM). Each Central Part
has its own dedicated I/O modules and/or shared I/O modules.
Redundant FSC-SMM
modules
The FSC-SM is configured for redundant operation. There can only be one
FSC-SMM in each Central Part.
In this configuration, each FSC-SMM is independently connected to the
UCN. One of the two will function as the primary, carrying out all UCN to
FSC-SM communication and data transfer operations. The other
FSC-SMM functions as the secondary or backup link between the UCN
and FSC. Database synchronization and status and control transfers
between the Primary and Secondary take place over the UCN.