
Main Menu
Alarms and Events
Alarm Group Indication
66
900 Control Station User Guide
Revision 9
May 2014
Alarm Group Indication
•
When there are no active alarms present, the background is gray with black text indicating NORMAL.
•
When any alarm within a group is active, the text is displayed in white color and the background turns
red.
•
For active, non-acknowledged alarms the background turns red, text changes to Unacknowledged and
flashes.
•
Once acknowledged, the alarm background remains red until the alarm condition goes away, the text
changes to Acknowledged and the background stops flashing.
•
If the alarm condition goes away (clears) before the operator acknowledges the alarm, the background
will turn yellow, the text will remain Unacknowledged and continue to flash until acknowledged.
Alarm Group Overview
The
Alarm Group
screen shows the status of each point present in the selected Alarm Group.