Setpoint Programmers
View/Edit Profile Segments
132
900 Control Station User Guide
Revision 9
May 2014
Item
Description
Auxiliary Value
Select a fixed soak value for this segment.
Guar Hold
Select ON to enable setpoint guarantee if Guaranteed Hold Type is Per
Segment.
Edit Events
Press the Edit Events 1-8 and Edit Events 9-16 buttons to display the event parameters.
You can configure 1 to 16 segment events to turn ON or OFF at the beginning of each segment. Segment
events are digital switches that provide ON/OFF outputs. When a segment event is turned ON, it remains
ON until the end of the segment at which time it is turned OFF unless it is configured to turn ON in the
next segment. Note that segment events are not interrupted by soak time delays when the process variable
is outside the guaranteed soak band. Events turn ON as soon as the previous segment is completed even if
the process variable has not reached the soak setpoint.
TIP
Events can be edited only while program is in READY state.