I/O Calibration
PPO Motor Calibration
Revision 9
900 Control Station User Guide
171
May 2014
Step
Action
5
Select “Calibrate 100”
•
Status
– Wait…Calculating 100% Feedback Value.
Feedback Value
– indicates the current position of the motor [0.0 to 1.0]
Percent Complete
– indicates the progress of this step [0 to 100%]
•
Status
– 100% Feedback Value Captured
6
Select “Calibrate Speed”. A warning will appear:
WARNING
MOTOR SPEED CALIBRATION
WILL MOVE MOTOR BETWEEN
THE 0% AND 100% CALIBRATION POINTS.
PRESS OK TO START
ELSE PRESS CANCEL
7
Press OK to start the Motor Speed Calibration.
•
Status
– Wait…Calculating Motor Speed.
Feedback Value
– indicates movement and direction of the motor [0.0 to 1.0]
Percent Complete
– indicates the progress of this step [0 to 100%]
•
Status
– Motor Speed Calibration Complete
8
Select “Save Cal”. The following information will appear:
Feedback At 0% - a value corresponding to the motor’s 0% position [0.0 to 1.0]
Feedback At 100% - a value corresponding to the motor’s 100% position [0.0 to 1.0]
Motor Speed (In Seconds). This is the motor speed that was detected during Motor Speed
Calibration. This is the time it takes the motor to travel from its calibrated 0% position to its
calibrated 100% position.
9
Press OK to Save Calibration.
•
Status
– Wait…Saving Calibration Values.
Feedback Value
– indicates the current position of the motor [0.0 to 1.0]
Percent Complete
– indicates the progress of this step [0 to 100%]
•
Status
– Calibration Completed