Process Displays
Alternator
Alternator Edit Setup display
108
900 Control Station User Guide
Revision 9
May 2014
Item
Description
Output Sequence
Integer between 0 and 16
“0” indicates the output is not in the Output sequence.
Examples of reasons to change it include:
•
If you are having trouble with a motor or pump (e.g., a bearing is going
bad) and you want to limit the amount of time it is used.
•
If you have 3 motors and one uses more electricity than another, you
may want to use two small motors first before you use the one large
motor. This could be handled by changing the sequence.
•
Taking a pump out of service for maintenance.
After editing, save the output sequence.