Process Displays
Alternator
Alternator Setup display
106
900 Control Station User Guide
Revision 9
May 2014
Alternator Setup display
Touch the blue title bar to edit the setup parameters.
Item
Description
Input Status
On or Off.
Output Status
Blank – Normal operating output (no designation)
DNR – Device Not Ready (see Alternator Operator display for example)
Output Sequence
Integer between 0 and 16
“0” indicates the output is not in the Output sequence.
Advance
Advances the output sequence. Not available for style DIRECT.
Edit
Select to edit the sequence. See Alternator Edit Setup.
Alternator Edit Setup display
Item
Description
Make/Break
MAKE – (Make before Break) Next output in the sequence is activated
before deactivating an output.
BREAK – (Break before Make) The output is removed before advancing
the sequence and activating the next output.
MAKE/BREAK is READ ONLY.
Max Out
Maximum number of outputs used.