AGA Detail Gas Components
Accessed from the AGA8 Detail widget, this display shows the values of the 21 gas components and other
setup parameters. You can edit the local values here.
Item
Description
Active Gas Component
Values
Local values: Uses Local Values of gas components.
Remote values: Uses the block’s Remote Values (input pin values from an online
analyzer).
Override Range Error
Under certain situations, the gas component values may exceed the expanded range
recommended by the AGA 8 Report. In Override mode a flow rate will be calculated. It
should be noted that calculated flow rates for conditions where the expanded range is
exceeded are outside of the recommended uncertainty values for AGA 8 calculations.
Sum of New Local
Values
When you edit the New Local Values this shows the sum of all 21 values. Values must
total 1.0 (100%).
Gas Component
This column lists the 21 gas components.
Local Values
This column lists the local value of each component.
Remote Values
This column lists the remote value of each component (via the AGA block input).
New Local Values
This column lets you enter new local values. Values must total 1.0 (100%). After
entering new values, Apply New Local Values.
Apply New Local Values
Select to transfer the New Local Values to the Local Values. These values do not take
effect unless Active Gas Component Values is set to Local Values, above.