Table 31 Device states
MONITORED
EVENTS
DEVICE STATES
READY
(Note 1)
PRE-
START
STARTING RUNNING
DISABLED
(Notes 1,2)
STOPPING
FAILED
Run Request
turns ON
X
X
Run Request
turns OFF
X
X
X
Disable (ON)
X
X
X
X
X
Disable (OFF)
X
Feedback from
Device
X
X
Device (ERR)
Fail ON
X
X
X
X
Device (ERR)
Fail OFF
X
Note 3
Reset (Rising
Edge)
X
Start Delay
Timer Expires
(edge)
X
Feedback Timer
Expires (edge)
X
X
Stop Delay
Timer Expires
(edge)
X
Note 1: If a device fails while in the state of READY or DISABLE, the device failure is not recognized until the
control goes into the PRESTART state.
Note 2: There are restrictions when the control goes into the Disable state from the Running State. The device is
immediately turned OFF without a Stop Delay. When the disable turns OFF, the control changes to the Ready
state.
Note 3: ERR Off (device fail) is monitored in Failed state, only if a) failed input caused the failure, and b) Auto Reset
is enabled.
Device Control Setup
Touch the blue title bar to access the setup display.
Item
Description
START DELAY
Current start delay time in seconds
STOP DELAY
Current stop delay time in seconds
FEEDBACK FAIL DELAY
Current feedback fail delay time in seconds