7.3.9.3
S
ERVICE
M
ENU
– N
ETWORK
– N
ODE
This menu allows you to set the network address and send/receive network parameters for the panel.
ENTER NODE NUMBER 0-240 >
TO DISABLE NETWORKING ON THIS FIP ENTER ‘0’
WARNING!! CHANGING THE NODE NUMBER CAN ALTER
NETWORK BEHAVIOUR AND SCRIPT PROCESSING.
MAKE SURE THE NETWORK CONFIGURATION IS
UPDATED TO REFLECT THIS CHANGE.
NETWORK NODE MENU
CURRENT NODE NO IS’0’
20 JULY 2002 14:44:37
A = 0
F = 0
I = 0
N = 1
DAY MODE
ESC
ENTER
BACKSP
Actions:
Follow the on screen prompts to enter a node
number. To remove the panel from the network,
enter Node 0.
If a non-zero node number is entered, you will be
further prompted to enter if you want the panel to
transmit events to the rest of the network
YES
or
to receive network events only without transmitting
them (mimic panel mode)
NO
.
7.3.9.4
S
ERVICE
M
ENU
– N
ETWORK
– R
ECEIVE
This menu is used to select which other nodes the panel will receive events from.
ENTER NODE NUMBER 0-240 >
NETWORK SETUP MENU
20 JULY 2002 14:44:37
A = 0
F = 0
I = 0
N = 1
DAY MODE
ESC
ENTER
BACKSP
Actions:
Enter the node number of the panel from which
the local node shall receive events.
Summary of Contents for BC-200
Page 1: ...BC 200 OPERATION INSTALLATION PROGRAMMING MANUAL P N DOC 01 013 ECN11 0058 23 Aug 12 Rev 5 07 ...
Page 138: ...Appendix BC 200 Manual P N DOC 01 013 138 9 12 PANEL EXPANSION RELAYS ...
Page 142: ...Appendix BC 200 Manual P N DOC 01 013 142 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E ...
Page 144: ...Appendix BC 200 Manual P N DOC 01 013 144 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E ...
Page 155: ......