Panel Operation
BC-200 Manual
– P/N DOC-01-013
49
7.3.3.15 S
ERVICE
M
ENU
– L
IST
– S
HADOW
This will display the shadow event history list in chronological order. Events are time stamped with date and time
and are shown in point and status format.
The BC-200 system stores over 4000 shadow history events. When the shadow history buffer is full, the system
will remove the oldest entries whenever a new entry is received thus leaving the 4000 most recent entries in the
list. This is an automatic process.
The shadow history cannot be erased.
As you scroll up and down the list, the currently highlighted item’s description is shown at the bottom of the
screen.
1: 23/10/98 10:45:56 1.1.Z1 ALARM
2: 23/10/98 10:50:02 1.1.Z1 ACKD ALARM
3: 23/10/98 10:55:34 1.1.Z1 RESET
4: 03/02/99 10:46:13 1.3.Z8 FAULT
5: 03/02/99 10:50:56 1.3.Z8 FAULT SELF CLEARED
6: 03/02/99 10:50:58 1.3.Z2 ISOLATED
7: 03/02/99 10:52:00 L1D1
ALARM
6: 03/02/99 10:50:58 L1D1
ACKD ALARM
IFS DAP700 MENU
IFS DAP700 MENU
IFS DAP700 MENU
IFS DAP700 MENU
IFS DAP700 MENU
SHADOW HISTORY LIST
28 JAN 1999 14:44:37
28 JAN 1999 14:44:37
28 JAN 1999 14:44:37
28 JAN 1999 14:44:37
28 JAN 1999 14:44:37
20 JULY 2002 14:44:37
DOWN
UP
USE BUTTONS/NUMBERS TO SELECT A FUNCTION
USE BUTTONS/NUMBERS TO SELECT A FUNCTION
USE BUTTONS/NUMBERS TO SELECT A FUNCTION
USE BUTTONS/NUMBERS TO SELECT A FUNCTION
USE BUTTONS/NUMBERS TO SELECT A FUNCTION
ZONE 1, SMOKE, LEVEL 6 APARTMENT 10
A = 0
F = 0
I = 0
N = 0
DAY MODE
BACK
PG DWN
PG UP
Actions:
Use the
UP
,
DOWN
,
PG UP
and
PG DWN
buttons
to scroll through the Shadow History List.
Pressing the
PG UP
button when you are on the first
page of the shadow history will wrap the list around
to the last page in the history.
The following events are recorded in the shadow history:
- Alarm
- Acknowledge Alarm
- Alarm Cleared
- Isolated Alarm
- Pre-alarm
- Pre-alarm Cleared
- Isolated Pre-alarm
- Isolated
- De-Isolated
- Fault
- Fault Cleared
- Isolated Fault
- System Faults
- Reset
Note:
You can also use the arrow keys, the Page Up and Page Dn keys on an external keyboard for scrolling
functions.
Summary of Contents for BC-200
Page 1: ...BC 200 OPERATION INSTALLATION PROGRAMMING MANUAL P N DOC 01 013 ECN11 0058 23 Aug 12 Rev 5 07 ...
Page 138: ...Appendix BC 200 Manual P N DOC 01 013 138 9 12 PANEL EXPANSION RELAYS ...
Page 142: ...Appendix BC 200 Manual P N DOC 01 013 142 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E ...
Page 144: ...Appendix BC 200 Manual P N DOC 01 013 144 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E ...
Page 155: ......