7.3.3.9
S
ERVICE
M
ENU
– L
IST
– L
IST
– AZF
This screen will display all conventional alarm zones (AZF’s) detected on the system. Zones which have been
allocated zone numbers will display the zone number, the physical point number (Ring/Module/I/O format), and
the zone description.
Unallocated zones will default to Z0 for the zone number, and the description will be the type of field module to
which the zone belongs. i.e. (AZM8 etc.)
00.001.Z01 (Z0
) PANEL BREAK GLASS
00.001.Z01 (Z0
) PANEL DOOR OPEN
x
01.001.Z01 (Z4
) CARPARK L4
01.001.Z02 (Z3
) CARPARK L3
01.001.Z03 (Z2
) CARPARK L2
01.001.Z04 (Z1
) CARPARK L1
I
01.001.Z05 (Z1
) LOBBY
01.001.Z06 (Z0
) (AZM8)
01.001.Z07 (Z0
) (AZM8)
01.001.Z08 (Z0
) (AZM8)
01.002.Z01 (Z12 ) LEVEL 1 CORRIDOR
01.002.Z02 (Z13 ) LEVEL 2 CORRIDOR
01.002.Z03 (Z212) ROOM 212
01.002.Z04 (Z213) ROOM 213
01.002.Z05 (Z214) ROOM 214
01.002.Z06 (Z10 ) LIFT MOTOR ROOM
F
01.002.Z07 (Z0
) (AZM8)
01.002.Z08 (Z0
) (AZM8)
ALARM ZONE LIST
20 JULY 2002 14:44:37
CHANGE
TEST
DOWN
UP
BACK
USE UP/DOWN BUTTONS TO SELECT A ZONE:
A = 0
F = 1
I = 1
N = 1
DAY MODE
Actions:
Use the
UP
and
DOWN
buttons to scroll through AZF
points.
When highlighting an AZF input point, pressing the
TEST
button will take you into the test menu for
AZF’s (refer page 71) providing the options for an
alarm and fault test.
Pressing the
CHANGE
button will take you to the
modify point screen (refer to page 59)
Pressing the
BACK
button will return you back to the
service menu
In the above example, the following abbreviations of STATUS apply.
Status
Abbreviation
Meaning
A
Alarm
I
Isolated
F
Fault
X
Activated
Note:
You can also use the arrow keys, the Page Up and Page Dn keys on an external keyboard for scrolling
functions.
Summary of Contents for BC-200
Page 1: ...BC 200 OPERATION INSTALLATION PROGRAMMING MANUAL P N DOC 01 013 ECN11 0058 23 Aug 12 Rev 5 07 ...
Page 138: ...Appendix BC 200 Manual P N DOC 01 013 138 9 12 PANEL EXPANSION RELAYS ...
Page 142: ...Appendix BC 200 Manual P N DOC 01 013 142 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E ...
Page 144: ...Appendix BC 200 Manual P N DOC 01 013 144 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E ...
Page 155: ......