Panel Operation
BC-200 Manual
– P/N DOC-01-013
59
7.3.5.1.1 S
ERVICE
M
ENU
– C
ONFIG
– AZF
Once you have selected the AZF you wish to change you will be in the “Modify Point” screen as follows:
SELECTED POINT: 1.1.Z1
NAME.
>
ZONE NO.
>
POINT TYPE >
ALARMED? (Y/N) > Y
LATCHED? (Y/N) > Y
AVF?
(Y/N) > N
TIMED?
(Y/N) > N
MODIFY POINT
20 JULY 2002 14:44:37
BACKSP
PLEASE ENTER THE INFORMATION BELOW:
Use arrows to move
around. INS,DEL to edit
lines. ENTER accept
line and/or Skip to
next item ESC to leave
this screen
Overwrite mode
A = 0
F = 0
I = 0
N = 1
ESC
ENTER
DAY MODE
Actions:
Use the external QWERTY keyboard to enter
descriptors
Press the
ENTER
button to move to the next line
Use soft
YES
and
NO
buttons as appropriate.
ESC
will take you back to the previous screen
If a zone number other than zero is entered, you will
be prompted to enter a zone name. A previously
named zone will automatically display the zone
name.
Once all entries have been completed you will be
prompted to save changes (Yes/No). If you select
no, changes to the point will be ignored.
The following data may be entered:
Item
Description
NAME
This is the descriptor for the AZF e.g. “LIFT MOTOR ROOM L16”. Up to 28 characters are
allowed.
ZONE NUMBER
This is the Zone number assignment of the AZF. One AZF per Zone. Allowed Zone
numbers are 1 to 999. An unnamed zone will prompt you for a zone name.
POINT TYPE
Type of point: e.g. FIRE, HEAT, SMOKE, FLAME, FSW, MCP, VMD, PSW, SPR. This
information is purely for display purposes when in Fire Fighter’s display mode.
ALARMED (Y/N)
Determines if the AZF is to be a full alarm point or a non-alarm input used for logic purposes
only.
LATCHED (Y/N)
Determines if the AZF is to be latching or non-latching type.
AVF (Y/N)
Determines if the AZF is to utilise the Alarm Verification Facility. (See Appendix for
explanation of AVF)
TIMED (Y/N)
Determines if the AZF is to be a time controlled input for use with Duct Probe detectors.
Refer Appendix for additional details).
Note:
If the Selected Point already has data, the existing data will be displayed. This data may be modified by
overwriting, or can be confirmed by just pressing the ENTER button for the field (using the soft or hard
buttons, or the Enter on the keyboard).
Overwrite/Insert mode can be toggled by pressing the Insert key on the remote keyboard.
Summary of Contents for BC-200
Page 1: ...BC 200 OPERATION INSTALLATION PROGRAMMING MANUAL P N DOC 01 013 ECN11 0058 23 Aug 12 Rev 5 07 ...
Page 138: ...Appendix BC 200 Manual P N DOC 01 013 138 9 12 PANEL EXPANSION RELAYS ...
Page 142: ...Appendix BC 200 Manual P N DOC 01 013 142 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E ...
Page 144: ...Appendix BC 200 Manual P N DOC 01 013 144 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E ...
Page 155: ......