Panel Operation
BC-200 Manual
– P/N DOC-01-013
77
7.3.7.3
S
ERVICE
M
ENU
– G
LOBAL
– D
AY
/N
IGHT
Each Analog addressable device has sensitivity setting for day mode and night mode. From this menu item you
can determine the changeover from Day > Night and Night > Day. To disable day / night mode, set both
changeover times to 00:00.
Current day / night mode is displayed in the top left of all screens.
1) SYSTEM
SET GLOBAL PARAMETERS
2) TIME
SET THE DATE/TIME
3) DAY-NIGHT
SET DAY/NIGHT TIMES
4) PASSWORDS
SET PASSWORDS
5) SITE
SET NAME & CONTACT INFO
DAY->NIGHT CHANGE OVER 2045 Change? >
NIGHT->DAY CHANGE OVER 0630
Change? >
ENTER TIME IN 24HR FORMAT
IN HOURS AND MINUTES.
e.g. 0630 (DAY), 2045 (NIGHT)
GLOBAL CONFIGURATION MENU
BACKSP
ENTER
SELECT A FUNCTION
20 JULY 2002 14:44:37
A = 0
F = 0
I = 0
N = 1
DAY MODE
ESC
Actions:
Use the numerical keypad or external keyboard to
type in the new Day -> Night change over time in
24 hour format e.g. 2045 and then press the
ENTER
button or just press the
ENTER
button
to accept the current time.
Use the numerical keypad or external keyboard to
type in the new Night -> Day change over time in
24 hour format e.g. 0630 and then press the
ENTER
button or just press the
ENTER
button
to accept the current date.
Once you have correctly entered the new times,
you will automatically return back to the service
menu
Note:
NP1000 can be used to force the panel into night mode. On V5.02 and above firmware if NP1000 is active, the
panel will be forced to operate in night mode and stays in night mode as long as NP1000 is active. This
feature allows the programmer to use scripting for switching between day/night modes.
7.3.7.4
S
ERVICE
M
ENU
– G
LOBAL
– P
ASSWORDS
Overview:
The BC-200 supports a total of 15 passwords. Passwords consist of 3 different levels. Each level can have 5 user
passwords (refer to 95 for a full description of password access levels).
If the Level 3 User 1 password is left blank (or a zero is used at the beginning of this field), then passwords are
disabled on the system. This may be useful during commissioning and/or small installations. Setting this password
back to zero at any time will disable all passwords on the system.
Only level 3 (highest) has the ability to change the passwords on the system.
Level 3 access should only be given to responsible persons with full authority to modify or delete the system
configuration.
Various different screens on the system require passwords (level 1, 2, or 3) and the user will be prompted for a
password on entry to those screens. Once a password has been entered, it will remain valid until logged out from
the service menu.
If a user does not log out using the log-out option on the service menu, they will be automatically logged out 5
minutes after the last button press to avoid systems remaining open to modification.
Summary of Contents for BC-200
Page 1: ...BC 200 OPERATION INSTALLATION PROGRAMMING MANUAL P N DOC 01 013 ECN11 0058 23 Aug 12 Rev 5 07 ...
Page 138: ...Appendix BC 200 Manual P N DOC 01 013 138 9 12 PANEL EXPANSION RELAYS ...
Page 142: ...Appendix BC 200 Manual P N DOC 01 013 142 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E ...
Page 144: ...Appendix BC 200 Manual P N DOC 01 013 144 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E ...
Page 155: ......