Panel Operation
BC-200 Manual
– P/N DOC-01-013
68
7.3.6.5
S
ERVICE
M
ENU
– A
NALOG
– L
OOP
This menu item allows several diagnostic functions to be performed on the loops themselves. Firstly you will be
prompted to enter a loop number. Then the screen will appear as follows:
LCM Version
-> 2.11
Loop wiring style
-> Open
Device led blink
-> ON
Detector Poll Style
-> FLASHSCAN
Module Poll Style
-> FLASHSCAN
ANALOG MENU - LOOP
20 JULY 2002 14:44:37
OFF
NEXT
MENU
LOOP 1 SELECTED:
A = 0
F = 0
I = 0
N = 0
AUTOPRG
TOGGLE
DAY MODE
Soft button functions:
ON/OFF
-> Turn device LED blink ON/OFF
AUTOPROG -> Look for new devices on loop
TOGGLE
-> Change the poll mode on loop
Actions:
Use the
NEXT
buttons to move to the next loop.
Pressing the
OFF
button will turn device blinking off on
the selected loop. If device blinking is already off,
the button will toggle to
ON
.
Press the
AUOTPRG
button to Auto Program the
selected loop. This will add any new detectors and
modules placed on the loop.
Pressing the
MENU
button will return you to the
service menu.
Note:
Applicable to V4.xx and below firmware
If the panel is powered down all loops will initialise with led blinking on. Where required, led blinking needs to
be turned off manually after a power up; the panel will not save the state of led blink after a cold reboot.
7.3.6.6
S
ERVICE
M
ENU
– A
NALOG
– A
NALOG
This menu item allows you to set the Loop styles to either Open or Closed loops. The screen will appear as
follows:
LOOP
1 is Open Loop
LOOP
2 is Closed Loop
LOOP
3 is Closed Loop
LOOP
4 is Closed Loop
LOOP
5 is Closed Loop
LOOP
6 is Closed Loop
LOOP
7 is Closed Loop
LOOP
8 is Closed Loop
LOOP
9 is Closed Loop
LOOP 10 is Closed Loop
ANALOG MENU - LOOPS
20 JULY 2002 14:44:37
DOWN
UP
BACK
A = 0
F = 0
I = 0
N = 0
TOGGLE
DAY MODE
SET LOOP STYLE FOR INSTALLED LCM/LEM
Actions:
Use the
UP
/
DOWN
buttons to move to the next
loop.
Pressing the
TOGGLE
button will change the loop
style for the selected loop between Open and
Closed.
Pressing the
BACK
button will return you to the
previous menu.
Summary of Contents for BC-200
Page 1: ...BC 200 OPERATION INSTALLATION PROGRAMMING MANUAL P N DOC 01 013 ECN11 0058 23 Aug 12 Rev 5 07 ...
Page 138: ...Appendix BC 200 Manual P N DOC 01 013 138 9 12 PANEL EXPANSION RELAYS ...
Page 142: ...Appendix BC 200 Manual P N DOC 01 013 142 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E ...
Page 144: ...Appendix BC 200 Manual P N DOC 01 013 144 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E ...
Page 155: ......