Panel Operation
BC-200 Manual
– P/N DOC-01-013
40
7.3.3.7.2.2
Service Menu – List – List – Analog – Modules – Change
This screen will allow you to change Analog addressable module information and options on a point by point
basis. As modules can be either inputs or outputs, once the device type has been entered, the screen will change
to suit either an input or output as follows.
Input modules:
SELECTED POINT : L1M1
NAME
> BREAK GLASS MAIN FOYER
DEVICE TYPE
> FMM-101/MMX-1010 MINI MON
ZONE NO.
> 2
ZONE TYPE
> MCP
ALARMED?
(Y/N)
> Y
LATCHED?
(Y/N)
> Y
AVF?
(Y/N)
> N
ANALOG MENU – PROG
A = 0
F = 0
I = 0
N = 0
20 JULY 2002 14:44:37
BACKSP
ENTER
PLEASE ENTER THE INFORMATION BELOW
DAY MODE
ESC
Actions:
Press the
BACKSP
button to delete an incorrect
character.
Press the
ENTER
button to step through options.
Press the
YES
or
NO
buttons when highlighted
to answer Y/N options.
Use external QWERTY keyboard to edit descriptors
and zone types. Tab will scroll through the fields.
The numeric keypad can be used for number entries
only.
When entering device type, an option pick list will
appear at the bottom of the screen.
Refer to appendix for more information on options.
You will be prompted Yes/No to save changes when
finished.
Output modules:
SELECTED POINT : L1M10
NAME
> EWIS OUTPUT #1
DEVICE TYPE
> FRM-1/CMX-2 RELAY O/P
ANALOG MENU – PROG
A = 0
F = 0
I = 0
N = 0
20 JULY 2002 14:44:37
BACKSP
ENTER
PLEASE ENTER THE INFORMATION BELOW
DAY MODE
ESC
Actions:
Press the
BACKSP
button to delete an incorrect
character.
Press the
ENTER
button to step through options.
Press the
YES
or
NO
buttons when highlighted
to answer Y/N options.
Use external QWERTY keyboard to edit descriptors
and zone types.
The numeric keypad can be used for number entries
only.
When entering device type, an option list will appear at
the bottom of the screen.
Refer to appendix for more information on options.
You will be prompted Yes/No to save changes when
finished.
Once the output module name and type has been saved, you will then be transferred to the script entry screen
and be prompted to enter a script for the output. Please refer to page 90 for more information on entering scripts.
Summary of Contents for BC-200
Page 1: ...BC 200 OPERATION INSTALLATION PROGRAMMING MANUAL P N DOC 01 013 ECN11 0058 23 Aug 12 Rev 5 07 ...
Page 138: ...Appendix BC 200 Manual P N DOC 01 013 138 9 12 PANEL EXPANSION RELAYS ...
Page 142: ...Appendix BC 200 Manual P N DOC 01 013 142 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E ...
Page 144: ...Appendix BC 200 Manual P N DOC 01 013 144 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E ...
Page 155: ......