Galaxy 3 Series Programming Manual
76
01 Final
Zones programmed as
Final
initiate the unsetting procedure and terminate setting procedure; opening the
Final
zone when the system or group is set starts the entry timer; opening and then closing the
Final
zone
during the exit procedure sets the system or assigned groups, providing all the zones are closed. The opening
(
+
) and closing (
–
) of
Final
zones during the setting and unsetting procedures are recorded in the event log.
Pressing the
key when programming a
Final
zone doubles the entry time of the group.
Opening a
Final
zone during the exit time is not reported on the keypad as an open zone; the
Entry/Exit
Horns
bleep rapidly to indicate that the zone is open.
NOTE:
The termination feature of a
Final
zone can be extended to terminate the setting of multiple groups
by pressing the
key when assigning a group to the zone. Refer to the
Star Group Function
.
02 Exit
Zones that protect the entry and exit routes are programmed as
Exit
. During the setting and unsetting proce-
dures
Exit
zones have a non-alarm operation. If the
Exit
zone is activated while the system is set - without the
unsetting of the group being initiated - an
Intruder
alarm condition is activated.
Opening an
Exit
zone during the exit time is not reported on the keypad as an open zone; the
Entry/Exit
Horns
bleep rapidly to indicate that the zone is open.
NOTE:
The
Exit
zone can be assigned to multiple groups by pressing the key when assigning a group to
the zone. This allows an
Exit
zone to be activated in a group which is not currently being unset
without activating an
Intruder
alarm. Refer to the
Star
Group Function
.
03 Intruder
The
Intruder
function is inactive when the system is unset. When the system is set, activation of an
Intruder
zone causes a full alarm activation that requires to be reset with a code authorized for
System Reset
- refer
to option
51.6 = PARAMETERS.System Reset
and option
51.55.3 = PARAMETERS.Confirm.Reduce Reset.
All zones are programmed as
Intruder
by default; this includes the zones on RIOs that are added to the
system at a later date.
04 24 Hours
The
24 Hours
zone function is continuously operational. In the unset state, activation of the zone function
generates a local alarm condition (the
Intruder
outputs are not activated). If the zone is activated while the
system is set, the
24 Hours
function operates the same as an
Intruder
function and results in a full alarm
condition. The
24 Hours
zone function requires a system reset following an activation in both the set and unset
conditions.
05 Security
The operation of the
Security
zone function is identical to the
24 Hours
zone function, except a
Security
zone activation in the unset generates a local alarm (
Horn
outputs activated) that does not require a system
reset; any valid code (type 2 or above) cancels the alarm and resets the system. An activation in the set state
generates a full alarm that requires a system reset. The activation (
+
) and restoration (–) of
Security
zones is
recorded in the event log.
52 - Program Zones (cont’d)
Summary of Contents for 3-144
Page 1: ...Honeywell Security Galaxy 3 48C 3 144 3 144C 3 520 3 520C Programming Manual ...
Page 2: ......
Page 8: ...Galaxy 3 Series Programming Manual 2 ...
Page 30: ...Galaxy 3 Series Programming Manual 24 ...
Page 184: ...Galaxy 3 Series Programming Manual 178 ...
Page 188: ...Galaxy 3 Series Programming Manual A 4 ...
Page 202: ...Galaxy 3 Series Programming Manual C 2 ...
Page 212: ...2 Galaxy 3 Series Programming Manual ...