Galaxy 3 Series Programming Manual
96
18 E/E Horn (Latch)
The
Entry/Exit Horn
output has a dual function:
•
in an alarm condition its function is identical to that of the
Horn
output;
•
during the unsetting and setting of the system it is used to provide an indication on the
status of the system. The indication states are as follows:
•
General Alarm
-
ON 500 msecs. OFF 500 msecs.
•
Clear to Exit
-
Continuous
•
Exit interrupted
-
ON 100 msecs. OFF 100 msecs.
•
75% Exit Time
-
ON 200 msecs. OFF 200 msecs.
•
Set
-
ON 600 msecs. OFF 600 msecs (twice)
•
Normal Entry
-
ON 800 msecs. OFF 200 msecs.
•
75% Entry Time
-
ON 200 msecs. OFF 200 msecs.
•
Fire
-
ON 500 msecs. OFF 100 msecs.
•
Chime
-
ON 500 msecs. OFF 400 msecs (twice)
19 Part Set (Reflex)
The
Part Set
output is activated when the assigned groups on the system are part set. This output is a
Reflex
output and follows the part set and unset status of the groups.
20 Confirm (Latch)
The
Confirm
output is activated when there have been activations on two separate zones: the second activa-
tion must occur within the Confirm Time Window. The zones do not have to be in the same group, however,
both groups must be assigned to the
Confirm
output to allow activation. Cross-group confirmation is control-
led by the
Communications
programming in menu
56.1, Int Telecoms or 56.5, Ext Telecoms.
If signalling
is by DTMF format, cross-group confirmation will occur on groups that share the same confirm channel. In all
other signalling formats, cross-group confirmation will occur on groups that share the same account number.
NOTE:
The
Confirm
output is used to give positive identification that a genuine intruder alarm condition has
occurred and to minimise the possibility of false alarm activations.
21 Line Fail (Reflex)
The
Line Fail
output is activated whenever a
Line Fail
zone is active or the telecom module detects and
sustains a line failure for more than 30 seconds.
22 Video (Pulse)
The
Video
output is activated by the
Video
zone when the system is set. This output can be used to activate
video recorder or video transmission systems.
23 Comm Fail (Latch)
The
Comm Fail
output is activated whenever there is a communication failure on the telecoms module tel-
ephone line. A fail to communicate event overrides the remaining
Bell Delay
period.
53 - Program Outputs (cont’d)
Summary of Contents for 3-144
Page 1: ...Honeywell Security Galaxy 3 48C 3 144 3 144C 3 520 3 520C Programming Manual ...
Page 2: ......
Page 8: ...Galaxy 3 Series Programming Manual 2 ...
Page 30: ...Galaxy 3 Series Programming Manual 24 ...
Page 184: ...Galaxy 3 Series Programming Manual 178 ...
Page 188: ...Galaxy 3 Series Programming Manual A 4 ...
Page 202: ...Galaxy 3 Series Programming Manual C 2 ...
Page 212: ...2 Galaxy 3 Series Programming Manual ...